Spot drifts
A stuck valve, a badly set schedule, a boiler running at weekends, a water leak: the deviation shows up in the week’s figures, not the year’s.
Understanding
Measure, compare, act: the foundation of lasting energy savings.
Keeping a building’s energy accounts just as you would keep a company’s books: every meter is read regularly, and every consumption figure is converted, corrected for climate and compared. Energy accounting shows where the energy goes, spots drifts as soon as they appear and proves, with figures to back it up, what each action delivers.
| Month | kWh | DD | kWh/DD |
|---|---|---|---|
| October | 11,800 | 190 | 62.1 |
| November | 18,600 | 300 | 62.0 |
| December | 23,700 | 380 | 62.4 |
| January | 28,900 | 400 | 72.3 |
Drift: +16% per degree-day
In January, the building uses 16% more per degree-day than in the previous months: a drift that needs explaining, spotted as soon as the month ends.
Definition
A bill arrives late, often covers a whole year, mixes estimated instalments, taxes and standing charges, and says nothing about how the energy is used. Energy accounting starts from the meters: it records actual consumption at regular intervals, building by building and, where possible, use by use.
| The bill | Energy accounting | |
|---|---|---|
| Frequency | Once a year, with instalments that are often estimated | At least once a month; every day, or even every quarter of an hour, with automatic readings |
| Units | Euros, including taxes and standing charges | kWh, m³ and litres, then their cost and CO₂ emissions |
| Level of detail | One total per supply point | By meter, by building, by use, down to the individual room |
| Climate | Ignored: a mild winter looks like a saving | Taken into account through degree-days |
| What it is for | Paying | Understanding, comparing, acting and checking |
It does not replace the company’s accounts but complements them: set against the bills, the readings let you check them, and the savings measured translate into euros.
Why
Without monitoring, consumption can drift for months without anyone noticing; it is often a year-end adjustment bill that raises the alarm, far too late. Regular monitoring serves six purposes.
A stuck valve, a badly set schedule, a boiler running at weekends, a water leak: the deviation shows up in the week’s figures, not the year’s.
Which buildings, which uses, which rooms consume the most? Priorities are set on measurements, not on impressions.
After an investment or a new setting, climate-corrected consumption shows what has really been saved.
Meter readings taken on site can be compared with the readings and volumes on the bill: an incorrect estimate shows up immediately.
An accurate consumption profile is an asset when choosing a tariff, a contracted capacity or a supplier.
Simple figures, shared regularly, make efforts visible and help them last.
The method
Energy accounting is not a report you write once: it is a loop. You measure, compare and act, then measure again to check.
Buildings, heated floor areas, meters (gas, fuel oil, electricity, water, heat, photovoltaic generation), uses and occupancy hours. Each meter is given a name and a clear role.
On fixed dates, at least once a month. Automatic reading eliminates missed readings and reading errors, and goes down to the day or the hour: that is where drifts become visible.
To compare different energy sources, everything is converted to kWh: one litre of fuel oil is worth about 10 kWh, one m³ of natural gas 10 to 11.5 kWh depending on the calorific value shown on the bill. Cost and CO₂ emissions follow from this.
A mild winter lowers heating consumption without any effort at all. Degree-days bring every period back to the same reference climate: at last, you compare like with like.
Month on month, year on year, between similar buildings and against benchmark values in kWh/m². Every deviation becomes a lead for action.
Settings, schedules, controls, building work: every action is dated. The following readings show whether the expected saving is really there, and whether it lasts.
The loop starts again at step 2: each new reading feeds the next analysis.
Degree-days
Heating needs depend first and foremost on the outdoor temperature. Degree-days measure how harsh the climate is: each day, you take the difference between a base temperature and the average outdoor temperature, if it is positive, then add up these differences over the month or the year.
The calculation, day by day
Degree-days = base temperature − average outdoor temperature of the day
If the day is warmer than the base, the result is zero: the building needs no heating.
In Belgium, the 15 °C and 16.5 °C bases are the most widely used. The base is the outdoor temperature above which heating is no longer needed: the sun, the occupants and the appliances then provide enough heat.
| Winter | 2024-2025 | 2025-2026 |
|---|---|---|
| Gas consumption (kWh) | 152,000 | 149,000 |
| Degree-days | 2,180 | 2,410 |
| kWh per degree-day | 69.7 | 61.8 |
For the same climate: consumption normalised to a reference winter of 2,300 degree-days.
Strictly speaking, only the heating share depends on the climate. Domestic hot water, cooking or boiler losses in summer do not: the energy signature makes it possible to separate them.
Energy signature
Plot each month of the year on a graph: degree-days on the horizontal axis, consumption on the vertical axis. The points fall almost on a straight line: this is the building’s energy signature. It tells you three things.
Divided by the heated floor area, annual consumption gives a ratio in kWh/m² that places the building on a scale from A++ to G. Calculated from actual consumption, this rating is indicative: it does not replace the EPB certificate, which is drawn up by a certifier based on the building’s characteristics.
Indicators
A few indicators are enough, as long as they are tracked regularly and always compared with something: the same period of the previous year, a similar building or a benchmark value.
kWh/m²
Compares buildings of different sizes and positions them against the benchmark values for their category (offices, schools, care homes…).
kWh/DD
Tracks heating performance from one period to the next, whatever the weather.
kWh
What the building consumes at night, at weekends or in summer. A rising base load points to a forgotten appliance, a schedule gone wrong or a leak.
h
With room-by-room control, each room’s heating hours show where the heat goes.
€
kWh multiplied by your tariffs: savings can also be read in euros.
kg CO₂
Each energy source has its own emission factor: the kWh saved become kilos of CO₂ avoided.
Proving savings
Comparing two bills proves nothing: the climate, occupancy or schedules may have changed in the meantime. The international IPMVP protocol describes the right method, and energy accounting provides the data.
Savings = adjusted baseline consumption − measured consumption
With AIDHOM
At AIDHOM, energy accounting is combined with remote management: the equipment that controls the heating also measures consumption, and ECO-MANAGER analyses it. No more manual readings or spreadsheets to keep up to date.
M-Bus meters are read by the ECO-CHES M-Bus master card. The ECO-IOT counts the pulses from gas, water or electricity meters, reads digital electricity meters through their P1 port and records the temperature probe readings.
In each room, the ECO-REG records heating times: consumption can be tracked down to the room, normalised to degree-days.
ECO-MANAGER calculates degree-days (base 16.5 °C by default, adjustable), compares them with the average of the last five years, plots the energy signature, gives the building’s rating and draws up energy balances in kWh, euros and CO₂.
Minimum and maximum thresholds for each meter trigger an email alert: abnormal water consumption or a drift is dealt with without waiting for the bill.
After installation, a test period of 2 to 8 weeks records the consumption of each room. These measurements are used to assess the possible savings and to set each room’s schedule with you.
Discover the softwareQuestions
Not necessarily. Many meters already have a pulse output, an M-Bus interface or, for electricity, a P1 port: they can be connected as they are. Otherwise, a sub-meter is fitted where the measurement is useful, for example on a heating circuit or on the hot water.
Once a month is the minimum to follow the trend. To spot a drift quickly, a daily or even hourly reading is far more effective: that is the whole point of automatic readings.
An audit is a snapshot: it analyses the building at a given moment and proposes improvements. Energy accounting is a film: it tracks consumption continuously, shows the effect of each action and spots drifts.
The two complement each other: energy accounting gives the auditor reliable data, then checks that the recommendations bear fruit.
The EPB certificate assesses a building’s theoretical performance, calculated from its characteristics (insulation, installations) for standard use. Energy accounting measures actual consumption, with the building’s real occupants and schedules.
A large gap between the two is useful information in itself: it often points to a settings or usage problem.
Monitoring alone saves nothing: the savings come from the actions it triggers. But by showing drifts day by day and the effect of each setting, it makes those actions possible and helps them last.
Room-by-room control then acts directly on the areas identified: our frequently asked questions include a worked example.
An energy manager, even part-time, who checks the figures every week and follows up on actions. With automatic readings and alerts, the time spent collecting data disappears: what remains is analysis and decision-making.